GM D 1063S ISOLATOR REPEATER

Model D1063S

Load Cell/Strain Gauge Bridge Galvanic Isolating Repeater

  • Up to four 350 Ω load cells in parallel or twelve 1000 Ω in parallel
  • High accuracy
  • High reliability, SMD components
  • EMC compatibility to EN61000-6-2, EN61000-6-4
  • ATEX approved
  • Simplified installation using standard DIN rail and plug-in terminal blocks
TECHNICAL SUPPORT
SALES
1530 5

The D1063S acts as transparent and very accurate galvanic isolated interface installed between a weighing indicator/system in the Safe Area and a load cell (or group of load cells) in a Hazardous Location. The output to the indicator/system is a transparent reflection of a single load cell equivalent to the one/s in the field. The unit located in Hazardous Location repeats with isolation the mV signal output to drive the load in the Safe Area dependent upon the host system reference voltage. Up to four 350 Ohm load cells, or six 400 Ohm load cells, or twelve 1.000 Ohm load cells can be connected in parallel. In addition a field-wiring fault LED indicates any lead break in the Hazardous Location side. Approved for Div. 2 installation.

Hazardous area:

Up to four 6 wire paralleled load cells 350 Ohm, 5 V, 80 mA total capacity.

Safe area:

mV corresponding to Input Bridge voltage. Accuracy, after system calibration: 0.003 %.

Function:

1 channel I.S. input from strain gauge signals, provides 3 port isolation (input/output/supply) and repeats, as a transparent unit, bridge signal output.